Size Range: 1/2" through 30"
Material: Carbon steel
Finish: Plain or Galvanized, also available plastic or epoxy coated
Service: Recommended for the suspension of stationary pipe lines.
Maximum Temperature: Plain 650° F, Galvanized and Epoxy 450° F
Approvals: Complies with Federal Specification A-A-1192A (Type 1), WW-H-171-E (Type 1) and MSS-SP-69 (Type 1). UL, ULC Listed and FM Approved (Sizes 3/4" through 8").
Installation: Hanger load nut above clevis must be tightened securely to assure proper hanger performance. When an oversized clevis is used, a pipe spacer should be placed over the clevis bolt as a spacer to assure that the lower U-strap will not move in on the bolt. For ductile iron pipe sizes, see Figure 590.
Adjustment: Vertical adjustment without removing pipe may be made from 3/8" through 5 1/8", varying with the size of clevis. Tighten upper nut after adjustment.
Features:
Punched forming holes may be present on certain sizes of this clevis hanger. These holes are solely for the purpose of manufacturing, and do not effect the structural integrity or load carrying capacities of these hangers.
"Span" represents the maximum recommended distance between hangers on a continuous and straight run of horizontal standard weight steel pipe filled with water. In all cases, verify that chosen location of hangers does not subject hangers to a load greater than the maximum recommended load shown above.
Indicates that span represents the maximum span for water filled pipe.
Material: Carbon steel
Finish: Plain or Galvanized, also available plastic or epoxy coated
Service: Recommended for the suspension of stationary pipe lines.
Maximum Temperature: Plain 650° F, Galvanized and Epoxy 450° F
Approvals: Complies with Federal Specification A-A-1192A (Type 1), WW-H-171-E (Type 1) and MSS-SP-69 (Type 1). UL, ULC Listed and FM Approved (Sizes 3/4" through 8").
Installation: Hanger load nut above clevis must be tightened securely to assure proper hanger performance. When an oversized clevis is used, a pipe spacer should be placed over the clevis bolt as a spacer to assure that the lower U-strap will not move in on the bolt. For ductile iron pipe sizes, see Figure 590.
Adjustment: Vertical adjustment without removing pipe may be made from 3/8" through 5 1/8", varying with the size of clevis. Tighten upper nut after adjustment.
Features:
- Design has yoke on outside of lower U-strap so yoke cannot slide toward center of bolt, thus bending of bolt is minimized.
- Sizes 5" and up have rod and two nuts instead of bolt and nut; thread length on clevis rod is such that the thread locks the nuts in place, and threads are not in shear plane.
Punched forming holes may be present on certain sizes of this clevis hanger. These holes are solely for the purpose of manufacturing, and do not effect the structural integrity or load carrying capacities of these hangers.
"Span" represents the maximum recommended distance between hangers on a continuous and straight run of horizontal standard weight steel pipe filled with water. In all cases, verify that chosen location of hangers does not subject hangers to a load greater than the maximum recommended load shown above.
Indicates that span represents the maximum span for water filled pipe.
Unit of Measure
Pipe Size |
N/A 14 inches |
Span |
N/A 25 ft. |
Rod Size - A |
N/A 1 inches |
Dimension - B |
N/A 12 9/16 inches |
Dimension - C |
N/A 19 9/16 inches |
Rod Take Out - E |
N/A 10 11/16 inches |
Adjustment - F |
N/A 2 11/16 inches |
Dimension - G |
N/A 3/4 inches |
Maximum Temperature (Plain) |
N/A 650 °F |
Maximum Temperature (Galvanized and Epoxy) |
N/A 450 °F |
Maximum Load |
N/A 4200 lbs |
Weight |
N/A 12.50 lbs |
Material |
N/A Carbon Steel |
Finish |
N/A Epoxy Coated Galvanized Plain Plastic Coated |