Features
  • Factory installed and wired
  • Battery Strength Indication
  • Field selectable Normally Open or Normally Closed
  • Nema 4x (IP 65) enclosure
Benefits
  • Reduces field installation cost
  • Provides visual and electronic indication of low battery state
  • Application Flexibility
  • Suitable for outdoor use, subject to ambient temperature limits
The Battery Backup (BBU) option for the Bray Series 70 24VAC actuators provides a convenient and cost effective solution to provide return of the valve or damper to a user-more
Unit of Measure

Specifications

Torque

600 lb·in
Features1 Auxiliary Switches Heater Modulating On/Off

Power Requirements

24 to 27 VAC

Battery Strength Alarm (Contact Ratings)

2 A

Operating Temperature Limits

-4 to 122 ºF-20 to 50 ºC

Battery Charging Temperature Limits

-4 to 122 ºF-20 to 50 ºC

Storage Temperature Limits

-40 to 140 ºF-40 to 60 ºC

Type of Batteries

SLA (Sealed Lead Acid) Power Sonic PS1212 or Equal

Life of Batteries

4 years, depended on ambient Temperature

Charging of Batteries

Continuous

Discharging of Batteries

4.2A (Only upon loss of input power)

Housing

Die Cast aluminum, Polyester finish, Nema 4X (IP 65)

Conduit Entries Wiring

3/4" NPT

Terminal Block Wiring

Max 14 AWG
  • 1 Use Battery Backup (BBU) only to control equipment under normal operating conditions. Where failure or malfunction of the electric actuator could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the electric actuator.