For Steam Service up to 600 psig (42 bar)...Capacities to 2,500 lb/hr (1,134 kg/hr)

The Armstrong CD-33 is a disc style trap designed to control the trap's cycle rate. By reducing the cycle rate, the Armstrong CD-33 will have a longer service life than typical disc traps. This enhanced performance will ensure that maintenance time is minimized and steam costs are greatly reduced.

The CD-33 is designed with three discharge ports, which offer stable disc operation to extend trap operating life. The capacities of the Armstrong CD-33 have been engineered specifically for the following applications: large steam main drips, process equipment, and HVAC heating equipment on constant pressure. The CD-33L (low capacity 1/2" and 3/4" only) trap is designed for the low capacity applications of steam main drips and steam tracing lines. By ensuring that the capacities are designed to suit the application, and are not oversized, the CD-33 Series will last longer than other disc traps with excessive capacity ratings.

Advantages
  • Three discharge port design
  • Minimum wear with controlled cycling
  • Freeze-resistant
  • Hardened seat and disc
Specification
Steam trap shall be stainless steel thermodynamic type, integral seat design with hardened disc and seating surfaces, and electroless nickel plated finish. When required, trap shall be supplied with an integral Y strainer, integral blowdown valve or rain guard insulating cap. Maximum allowable pressure (vessel design) shall be 915 psig @ 752ºF (63 bar @ 400ºC). Maximum operating pressure shall be 600 psig @ 752ºF (41 bar @ 400ºC).
Unit of Measure

Specifications

Body

N/A ASTM A743 Gr. CA40

Cap

N/A ASTM A743 Gr. CA40

Disc Material

N/A ASTM A276 Gr. 420

Strainer Screen

N/A 30 x 30 Mesh T-304 Stainless Steel

Screen Retainer

N/A ASTM A743 Gr. CA40

Pipe Connections

N/A 1 in1/2 in3/4 in15 mm20 mm25 mm

Dimension - A

N/A 1 7/16 in1 3/4 in37 mm44 mm

Height - B

N/A 2 1/2 in3 1/8 in63 mm79 mm

Length - C

N/A 3 5/16 in3 15/16 in84 mm100 mm

Top of Cap - D

N/A 1 3/4 in2 1/4 in44 mm57 mm

Weight

N/A 1.4 lb2.5 lb0.64 kg1.1 kg

Maximum Allowable Pressure at 752ºF (Vessel Design)

N/A 915 psig

Maximum Allowable Pressure at 400ºC (Vessel Design)

N/A 63 bar

Minimum Operating Pressure

N/A 3.5 psig0.24 bar

Maximum Operating Pressure at 486ºF

N/A 600 psig

Maximum Operating Pressure at 252ºC

N/A 41 bar

Maximum Back Pressure of Inlet Pressure

N/A 80 %

Options

N/A Blowdown Valve (Stainless Steel) Rain Guard Insulating Cap (1/2'', 3/4'' Sizes Only) (Stainless Steel)

Note

N/A Designs, materials, weights and performance ratings are approximate and subject to change without notice.