Gauges indicate Air Loading, Air Supply and/or Delivery Pressures
Integral Filter Conditions Dirty Shop Air
50 PSI Delivery Pressure
Accurate Delivery Pressure over Wide Range of Flow
Typical Configurations For use with:
EA
Positioners
Any Controller Requiring Conditioned Pneumatic Signal
E8
EPC
Application Data
To display Air Loading, Air Supply anchor Delivery Pressure
To Remotely Adjust Air Pilots
To Reduce Plant Air Pressure to Instrument Air Pressure for Signaling Regulators and Control Valves
To Filter Plant Air to Instrument Air Quality
Specification Air Adjustment Panel shall provide remote control for air actuated regulators and control valves. It shall convert plant air to instrument quality air and provide 0 to 50 psi delivery pressure. The Panel shall have a flow capacity of 22 scfm. Panel shall have gauges indicating air load pressure and air supply pressure with option of process delivery pressure gauge.