Items |
70-24-0061SV-BBU Battery Backup for Series 70 Actuator |
70-24-0061SVH-BBU Battery Backup for Series 70 Actuator |
70-24-0201SV-BBU Battery Backup for Series 70 Actuator |
70-24-0201SVH-BBU Battery Backup for Series 70 Actuator |
70-24-0501SV-BBU Battery Backup for Series 70 Actuator |
|||||
Torque | N/A 600 lb·in | N/A 600 lb·in | N/A 2000 lb·in | N/A 2000 lb·in | N/A 5000 lb·in | |||||
Features1 | N/A Auxiliary Switches Modulating On/Off | N/A Auxiliary Switches Heater Modulating On/Off | N/A Auxiliary Switches Modulating On/Off | N/A Auxiliary Switches Heater Modulating On/Off | N/A Auxiliary Switches Modulating On/Off | |||||
Power Requirements | N/A 24 to 27 VAC | |||||||||
Current Draw (Actuator w/ BBU) | N/A 39 VA | N/A | N/A 51 VA | N/A | N/A 75 VA | |||||
Battery Strength Alarm (Contact Ratings) | N/A 2 A | |||||||||
Operating Temperature Limits | N/A -4 to 122 ºF-20 to 50 ºC | |||||||||
Battery Charging Temperature Limits | N/A -4 to 122 ºF-20 to 50 ºC | |||||||||
Storage Temperature Limits | N/A -40 to 140 ºF-40 to 60 ºC | |||||||||
Type of Batteries | N/A SLA (Sealed Lead Acid) Power Sonic PS1212 or Equal | |||||||||
Life of Batteries | N/A 4 years, depended on ambient Temperature | |||||||||
Charging of Batteries | N/A Continuous | |||||||||
Discharging of Batteries | N/A 4.2A (Only upon loss of input power) | |||||||||
Housing | N/A Die Cast aluminum, Polyester finish, Nema 4X (IP 65) | |||||||||
Conduit Entries Wiring | N/A 3/4" NPT | |||||||||
Terminal Block Wiring | N/A Max 14 AWG | |||||||||
|