Battery Backup for Series 70 Actuator
Electric Actuators
Features
The advanced circuitry of the BBU continuously monitors battery strength and provides a visual indication (LED) and remote indication (via dry contact). The BBU is housed in sturdy die cast aluminum NEMA 4x (IP 65) enclosure and is factory mounted and factory wired to the Bray Series 70 24 VAC actuator.
Operation
In the normal mode of operation with power supplied to the actuator, the batteries maintain a charge and are in an offline mode. The power applied to the motor is from the power supply, not the batteries.
Upon loss of supply power, after a 10 second startup sequence, the BBU circuitry applies the stored power in the batteries to move the valve or damper to the full open or full closed position designated by the user. The actuator remains in this position until external power is restored to the unit.
For two position (on/off units), and modulating units, the BBU board automatically detects when the actuator has reached the desired position and then disconnects the battery power from the motor.
- Factory installed and wired
- Battery Strength Indication
- Field selectable Normally Open or Normally Closed
- Nema 4x (IP 65) enclosure
- Reduces field installation cost
- Provides visual and electronic indication of low battery state
- Application Flexibility
- Suitable for outdoor use, subject to ambient temperature limits
The advanced circuitry of the BBU continuously monitors battery strength and provides a visual indication (LED) and remote indication (via dry contact). The BBU is housed in sturdy die cast aluminum NEMA 4x (IP 65) enclosure and is factory mounted and factory wired to the Bray Series 70 24 VAC actuator.
Operation
In the normal mode of operation with power supplied to the actuator, the batteries maintain a charge and are in an offline mode. The power applied to the motor is from the power supply, not the batteries.
Upon loss of supply power, after a 10 second startup sequence, the BBU circuitry applies the stored power in the batteries to move the valve or damper to the full open or full closed position designated by the user. The actuator remains in this position until external power is restored to the unit.
For two position (on/off units), and modulating units, the BBU board automatically detects when the actuator has reached the desired position and then disconnects the battery power from the motor.
Unit of Measure
Items |
/Asset/BBU-For-Series-70.jpg 70-24-0061SV-BBU Battery Backup for Series 70 Actuator |
/Asset/BBU-For-Series-70.jpg 70-24-0061SVH-BBU Battery Backup for Series 70 Actuator |
/Asset/BBU-For-Series-70.jpg 70-24-0201SV-BBU Battery Backup for Series 70 Actuator |
/Asset/BBU-For-Series-70.jpg 70-24-0201SVH-BBU Battery Backup for Series 70 Actuator |
/Asset/BBU-For-Series-70.jpg 70-24-0501SV-BBU Battery Backup for Series 70 Actuator |
|||||
Torque | N/A 600 lb·in | N/A 600 lb·in | N/A 2000 lb·in | N/A 2000 lb·in | N/A 5000 lb·in | |||||
Features1 | N/A Auxiliary Switches Modulating On/Off | N/A Auxiliary Switches Heater Modulating On/Off | N/A Auxiliary Switches Modulating On/Off | N/A Auxiliary Switches Heater Modulating On/Off | N/A Auxiliary Switches Modulating On/Off | |||||
Power Requirements | N/A 24 to 27 VAC | |||||||||
Current Draw (Actuator w/ BBU) | N/A 39 VA | N/A | N/A 51 VA | N/A | N/A 75 VA | |||||
Battery Strength Alarm (Contact Ratings) | N/A 2 A | |||||||||
Operating Temperature Limits | N/A -4 to 122 ºF-20 to 50 ºC | |||||||||
Battery Charging Temperature Limits | N/A -4 to 122 ºF-20 to 50 ºC | |||||||||
Storage Temperature Limits | N/A -40 to 140 ºF-40 to 60 ºC | |||||||||
Type of Batteries | N/A SLA (Sealed Lead Acid) Power Sonic PS1212 or Equal | |||||||||
Life of Batteries | N/A 4 years, depended on ambient Temperature | |||||||||
Charging of Batteries | N/A Continuous | |||||||||
Discharging of Batteries | N/A 4.2A (Only upon loss of input power) | |||||||||
Housing | N/A Die Cast aluminum, Polyester finish, Nema 4X (IP 65) | |||||||||
Conduit Entries Wiring | N/A 3/4" NPT | |||||||||
Terminal Block Wiring | N/A Max 14 AWG | |||||||||
|